4-67. CONTROL CIRCUIT BREAKERS (CB2 AND
CB3)
Preliminary procedure:
Pull safety control box out far enough to gain access to panel mounting screws.
Inspection/Test
a.
(1)
Check to see that power has been disconnected.
(2)
Using screwdriver, remove four flat head screws from safety control box panel.
Carefully pull panel from safety control box far enough to gain access to circuit breaker terminal connec-
(3)
tions.
(4)
Check that wire leads are properly connected. (See wiring diagram Figure 4-20.)
Check circuit breakers for signs of overheating or other visible damage.
(5)
Set circuit breaker reset bars In OFF position.
(6)
(7)
breaker CB3 and terminals A1 and A2 and B1 and B2 on circuit breaker CB2. All contacts should be open.
If there is continuity on any check, replace circuit breaker(s).
Press reset bars toward the OFF stop, then place them in the ON position.
(8)
(9)
A2 on circuit breaker CB3 and terminals A1 and A2 and B1 and B2 on circuit breaker CB2. All contacts
should be closed. If there is no continuity on any check, replace circuit breaker(s).