4.36 CONDENSER FAN, HOUSING AND MOTOR. - Continued
Location/Item
Action
Remarks
Installation
f. Secure service valves (21) to scroll housing (16)
Continued
using two screws (17), two Iockwashers (18), two
flat washers (19) and two clamps (20).
g. Install five screws (15) to secure scroll housing.
Take care to avoid damaging the con-
denser coil when installing the motor and
mounting plate in unit.
h. Place motor (14) and mounting plate (8) into
position in the housing.
Insert shaft extension (10) onto motor shaft (13).
i.
Align the shaft extension (10) with the impeller
j.
(12) and join together.
k. Tighten the setscrew (11) on the impeller (12).
l. Secure the motor mounting plate (8) to the hous-
ing using four screws (6) and four flat washers
(7).
m. Center impeller (12) in scroll housing (16) while
looking through the louver opening.
n. Tighten two setscrews (9) on the shaft extension
(10).
o. Connect the motor connections and remove tags.
p. Install the solenoid coil (4) onto the plunger (5)
with nameplate (3) and plunger nut (2).
q. Connect the electrical connector (1) for solenoid
coil L2 to the bulkhead.
r.
t.
Install rear and center top covers.
4-100