TM 9-4120-378-14
5.17 EXPANSION VALVES. - continued
Remarks
Action
Location/Item
Avoid bodily contact with liquid refrig-
erant and avoid inhaling refrigerant
gas. Be especially careful that refrig-
erant does not come in contact with
eyes. In case of refrigerant leaks, ven-
tilate area immediately.
Check that power source is discon-
nected. Check that system is dis-
charged of refrigerant.
When performing brazing/debrazing
operations, wrap valves with wet rags
to act as a heat sink.
NOTE
erant system is opened.
Primary
Expansion
Valve
a.
Soften mastic bulb in well (1) if necessary, by warm-
Removal
ing with a cloth soaked in hot water and wrung out,
a heat lamp, or equivalent.
Withdraw bulb (2) from well taking care to prevent
b.
damage to capillary tube.
c.
With dry nitrogen flowing through refrigerant sys-
tem, debraze tubing to valve at debrazing point.
d.
Remove expansion valve (3) from unit.
5-53