TM 9-4120-385-14
(g) Using a megger set on the 500 Vscale, check pins A, B, or C of J3 to
compressor housing. Reading should exceed 1 megohm. If reading is less, motor is burned out.
(h) If motor is burned out, perform cleanup procedures. Refer to
subparagraph c.
2.
WARNING
High voltage can kill.
(a) Disconnect power supply.
(b) Disconnect P3 from J3.
replaced. Continue testing to isolate defective component. See Figure 5-12.