5-18.
CHARGING
VALVES
(cont)
Figure
5-12.
charging
valves
c.
Installation.
(1)
Position
valve
in
unit
as
noted
during
disassembly.
(2)
Replace
filter
drier.
(See
paragraph
5-21.)
Purge
the
system
with
nitrogen.
(See
paragraph
5-6.)
(3)
Braze
the
charging
valve
in
place.
(See
paragraph
5-7.)
(4)
Leak
test
the
newly
connected
joints
and
all
connections
in
those
areas.
(See
paragraph
5-8.)
(5)
Evacuate
the
system.
(See
paragraph
5-9.)
(6)
Charge
system.
(See
paragraph
5-10.)
(7)
(8)
Close
condenser
access
door.