TM 9-4120-398-14
This task covers
a. Replacement
b. Repair
Tool kit, refrigeration SVC
Power OFF
Straightener, fin
Personnel
Condenser motor removed
2 people
Top panel and grille removed
System discharged
(Paragraph 5--5)
Air filter
WARNING
Filter-drier
Brazing Alloy
Voltages used can kill. Always
disconnect power cord to air conditioner
before performing any internal
maintenance. Shutting unit off at its
control panel does not disconnect
unit power.
Rags
Refrigerant -22
Death or serious injury may result if personnel fail to observe safety precautions. Use great care to
avoid contact with liquid refrigerant or refrigerant gas being discharged under pressure. Sudden and
irreversible tissue damage can result from freezing. Wear thermal protective gloves and a face protector
or goggles in any situation where skin-eye contact is possible.
Prevent contact of refrigerant gas with flame or hot surfaces. Heat causes refrigerant to break down and form
carbonyl chloride (phosgene), a highly poisonous and corrosive gas.