TM 9-4120-408-14
5-26. THERMOEXPANSION VALVE (TEV) MAINTENANCE
This task covers:
Remove
Install
Test and Adjust
INITIAL SETUP:
Tools
Materials/Parts (Continued)
Tool Kit, Service Refrigeration Unit,
Section III, Item 7
Section III, Item 9
Manifold Gage, Charging and Testing,
Refer to TM 9-4120-408-24P for part
numbers of items to be replaced.
Item 17
Equipment Conditions
Materials/Parts
5-18.
Equalizer Line Tube Assembly disconnected,
General Safety Instructions
Do not work on equipment without
following standard shop safety precautions.
CAUTION
Dehydrator must be replaced every time the air conditioner lines are exposed to the atmosphere.
Failure to obey this caution may result in equipment damage.
a. Remove.
NOTE
Insulation material must be removed from suction line tube assembly prior to removal of TEV sensing
bulb.
(1) Remove insulation from suction line tube assembly (Figure 5-22, 1).
(2) Remove two nuts (2), screws (3), and clamp (4) securing TEV sensing bulb (5) to side of suction line tube
assembly (1). Remove and discard tiedown straps.
(3) Loosen two flare nuts (6) and remove TEV (7).
Change 1 5-61