TM 9-4110-256-14
5-20.
CONDENSER COIL REPLACEMENT.
This task covers:
a. Removal
b. Installation
INITIAL
SETUP
Tools:
Materials/Parts:
Gloves
Self Locking Nuts (8)
Self Locking Nut (Pressure Regulator Clamp)
Equipment Conditions:
Self Locking Nuts (4) (Wire Harness Clamps)
Both side condenser doors open.
Lock Washers (3)
a.
Removal.
(1) Remove self locking nut (1) and bolt (2). Discard self locking nut.
WARNING
Coil fins are sharp and can cut hands or fingers. Wear gloves to prevent personal injury when
handling coil.
(3)
Remove eight self locking nuts (5), bolts (6), and condenser coil (4). Discard self locking nuts.
(4)
(5)
Remove four self locking nuts (8) and bolts (9). Discard self locking nuts.
(6)
Remove three bolts (10), lock washers (11), and condenser shroud (7). Discard lock washers.
b.
Installation.
(1)
If condenser shroud (7) was removed, install shroud, aline three clamps (12) and install new lock washers
(11) and bolts (10).
(2)
Aline four clamps (13) and install four bolts (9) and self locking nuts (8).
(3)
WARNING
Coil fins are sharp and can cut hands or fingers. Wear gloves to prevent personal injury when
handling coil.
(4) Install condenser coil (4), eight bolts (6), and new self locking nuts (5).
5-41