TM 9-4120-388-14
4-42. BLOCK OFF ASSEMBLY.
This part is supplied only when specified on air conditioner ordering information.
NOTE
This paragraph is applicable only to units with remote mounted control panels. See para-
graph 4-7, installation instructions, and your facility or
shelter manual.
b. Inspection
a. Removal
This task consists of:
d. Installation
c. Repair
INITIAL SET-UP:
Equipment Co ndition
Disconnect input power to the air conditioner before performing any internal
maintenance. Voltages used can KILL. Shutting the unit off at the control panel
does not disconnect unit power.
a. Removal.
(1) If the P7 plug is connected at the bulkhead connector, disconnect it.
(2) Pull connector from block off.
(3) If alternate location for power connector was used, remove the connector.
(4) Remove four screws from lower flanges.
(5) Remove block off assembly.