TM 9-4120-378-14
5.2 DIRECT SUPPORT TROUBLESHOOTING. See table 5-1.
Malfunction
Test or Inspection
Corrective Action
COMPRESSOR WILL NOT START
1.
Make continuity check of control circuit. See Appendix F for control circuit
Step 1.
a. Repair loose or broken connections.
Step 2.
Test starting relay or start capacitor. (Refer to paragraphs 4.27 and 4.29.)
Step 3.
Step 4.
Check continuity of HIGH and LOW pressure switches at room temperature.
Step 5.
a. If continuity does not exist. press reset button and recheck.
Check polarity of power input plug (P1 ) using voltmeter. With positive (+) lead in
Step 6.
pin A and negative (-) lead in pin B, voltage should be115 Vac. With positive (+)
lead pin A and negative (-) lead in pin D, voltage should be 115 Vat. With positive
(+) lead in pin B and negative (-) lead in pin D, voltage should be zero volts.
Replace power input plug (P1 ) which does not pass above test.
2.
COMPRESSOR STARTS, BUT STOPS AT ONCE - "SHORT CYCLES"
Step 1.
Inspect evaporator coil for dirt or icing, and check for obstructions at outlet louver.
Step 2.
b. Defrost in HEAT mode, or remove obstructions from outlet louver.