TM 9-4120-378-14
5.26 LIQUID INDICATOR-REPLACE. This task covers removal and installation.
INITIAL SETUP
Materials/Parts:
Equipment Conditions:
Action
Remarks
Location/Item
Check that power source is discon-
nected. Check that refrigerant system
is discharged.
Removal
With a steady flow of dry nitrogen through refrigera-
tion system, debraze liquid sight indicator from con-
denser coil and attached tubing.
Installation
a.
tion system, braze liquid sight indicator onto con-
denser coil and tubing.
b.
c.
Leak check refrigeration system.
d.
Evacuate refrigerant system.
e.